Permit Number: T05CM05922
Parcel: 11515100B

Address:
2005 N 13TH AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05922
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2005 JIM EGAN FIRE REVIEW Approved
11/30/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The minimum font size shall be 1/8".
2. The specified water closet is illegal per ARS 45-313.
3. Show how the connection for the condensate drain shown on the soil & vent riser diagram complies with the 1994 UPC.
4. Clarify the size of the existing CW pipe to which the new spiping is being connected. It is shown as both 1" and 3/4". If it is 3/4", show the existing load it is serving.
5. Provide heat traps and pipe insulation for the water heater per Section 804, IECC 2003.
6. The water pressure calculations do not support using a 1/2" pipe to serve a water closet.
7. Show the "approved manner" for attaching the water heater to the wall structure. Note that the water heater is shown as being mounted "above ceiling" and at a maximum height of 5'-0". Please clarify.
11/30/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Provide vertical grab bar per section 604.5.1 and 604.4.2.
11/30/2005 ROBERT SHERRY WATER REVIEW Approved
11/30/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The minimum font size shall be 1/8".
2. Provide an auxiliary/secondary drain system for the fan coil unit. Reference Section 307.2.3, IMC 2000.
3. Show how EF-1 will be controlled to prevent recirculation of the air supplied to the restroom. Reference Section 403.2.1 (3), IMC 2000.
4. Provide duct insulation per Section 803.2.8, IECC, 2003.
5. The plumbing plan shows the condensate drain terminating outside the building. SHow that the termination point complies with Section 307.2.1, IMC 2000 as amended by the City of Tucson.
12/01/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM05922 12/1/05

1. Provide a disconnect for the Water Heater per NEC 422 Part III.
2. Sheet A3 indicates WH is 4.5 KW. Only 1650 VA per panel schedule. Coordinate with Plumbing and clarify.
3. HPCU-1 with 36.3 FLA, shall not be on a 20A Ckt.
4. 1/0 panel feeder has 150A ampacity. Reference NEC Table 310.16. Not protected by a 200A CB.
5. Provide service load calculations.
12/14/2005 GBONILL1 WWM REVIEW Needs Review
12/14/2005 GBONILL1 ZONING REVIEW Needs Review
12/14/2005 GBONILL1 ENGINEERING REVIEW Needs Review