Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - WALK THRU
Permit Number - T05CM05910
Review Name: REVISION - WALK THRU
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/20/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the plumbing plan to include the 3" WCO on the waste and vent riser diagram. 2. The water pipe sizing shown on the revised water riser diagram is not supported by the pipe sizing calculations shown on P0.1. 3. Revise the plumbing plan to show the location of the vents. 4. Clarify the extent of the curret revisions (i.e. label the current revision cloud and do not show the previous revision clouds). |