Permit Number: T05CM05910
Parcel: 12108281A

Review Status: Completed

Review Details: REVISION - WALK THRU

Permit Number - T05CM05910
Review Name: REVISION - WALK THRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the plumbing plan to include the 3" WCO on the waste and vent riser diagram.
2. The water pipe sizing shown on the revised water riser diagram is not supported by the pipe sizing calculations shown on P0.1.
3. Revise the plumbing plan to show the location of the vents.
4. Clarify the extent of the curret revisions (i.e. label the current revision cloud and do not show the previous revision clouds).