Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T05CM05862
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/27/2006 | MARTIN BROWN | FIRE | REVIEW | Denied | 1.) Minimum 20 ft. wide, paved access onto property per IFC, 2003, Section 503.2.3 and City of Tucson fire code amendment for the same section. 2.) Show existing fire hydrant locations. |
| 02/28/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | A City of Tucson approved site plan is required to be submitted with the building plan. Please submit one copy of the City approved site plan. Zoning and Engineering approval stamps must be on the site plan. |
| 03/01/2006 | RBABBIT1 | LANDFILL | REVIEW | Approved | |
| 03/02/2006 | GERRY KOZIOL | WWM | REVIEW | Denied | needs to show method/location of connection to public sewer. needs wastewater/IWC review/approval (TomTomchak-579-5771) needs 8th floor credit evaluation |
| 03/08/2006 | ROBERT SHERRY | WATER | REVIEW | Denied | Show the location of the reduced pressure backflow assembly on the drawings, specify the reduced pressure backflow assembly being installed, and indicate the size of the assembly. Reference City of Tucson Ordinance 9976, Backflow Prevention and Cross-connection Control. |
| 03/27/2006 | PETER MCLAUGHLIN | ZONING | REVIEW | Denied | Zoning 3/27/06 An approved site plan is required. Note: A notarized and recorded lot combination is required prior to approval of site plan. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/30/2006 | ADRIANNE OLIVO | OUT TO CUSTOMER | Completed |
| 03/30/2006 | SUE REEVES | REJECT SHELF | Completed |