Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/21/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
11/21/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
11/21/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
11/22/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
11/22/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/22/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/22/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM05801 11/22/05 1. Show transformer grounding as a Separately Derived System. Reference NEC 250. 2. Please change the 20A CB for FCU-1 to a 15A CB, unless the manufacturer recommends otherwise. |
11/28/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how recirculation of the air supplied to the restroom will not be recirculated when the exhaust fan is turned off. Reference Section 403.2.1 (3), IMC 2000. |
11/30/2005 | GERRY KOZIOL | WWM | REVIEW | Completed |