Permit Number: T05CM05801
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05801
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2005 JIM EGAN FIRE REVIEW Approved
11/21/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
11/21/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
11/22/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/22/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
11/22/2005 ROBERT SHERRY WATER REVIEW Approved
11/22/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM05801 11/22/05

1. Show transformer grounding as a Separately Derived System. Reference NEC 250.
2. Please change the 20A CB for FCU-1 to a 15A CB, unless the manufacturer recommends otherwise.
11/28/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how recirculation of the air supplied to the restroom will not be recirculated when the exhaust fan is turned off. Reference Section 403.2.1 (3), IMC 2000.
11/30/2005 GERRY KOZIOL WWM REVIEW Completed