| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/21/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t05cm05788 11/21/05 1. "C" value on fault calculations is 22737, which indicates 350 MCM. Service entrance conductors on line diagram are 500 MCM. Please clarify. 2. (1) 500 MCM only has ampacity of 380A, which is not sufficient for 720.8A load. Please clarify. |