Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM05788
Parcel: 14029007C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM05788
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/21/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM05788 11/21/05

1. Receptacle outlets shall be computed at a minimum of 180 VA each yoke per NEC 220.3 (B) (9). For example, Ckt 4 shall be counted at 900VA, not 540. Typical.
2. Provide power requirements for the new WH on Sheet MP1.
3. Please verify with the manufacturer that the WH is cord-connected.
4. Fault calculations call length to New Panel as 115'. Could not be 115' because service is just on the other side of the wall. Please resubmit fault calculations.
5. Minimum font size 10 point.
11/21/2005 DAN CASTRO ZONING REVIEW Approved
11/21/2005 JIM EGAN FIRE REVIEW Approved
11/21/2005 JMORALE1 WWM REVIEW Needs Review