Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM05788
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/21/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
11/21/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM05788 11/21/05 1. Receptacle outlets shall be computed at a minimum of 180 VA each yoke per NEC 220.3 (B) (9). For example, Ckt 4 shall be counted at 900VA, not 540. Typical. 2. Provide power requirements for the new WH on Sheet MP1. 3. Please verify with the manufacturer that the WH is cord-connected. 4. Fault calculations call length to New Panel as 115'. Could not be 115' because service is just on the other side of the wall. Please resubmit fault calculations. 5. Minimum font size 10 point. |
11/21/2005 | DAN CASTRO | ZONING | REVIEW | Approved | |
11/21/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
11/21/2005 | JMORALE1 | WWM | REVIEW | Needs Review |