Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM05788
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/18/2005 | ANY | ENGINEERING | REVIEW | Approved | |
| 11/18/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide riser diagram for water and show the pipe sizes. |
| 11/18/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/18/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM05788 11/18/05 1. Provide a Lighting fixture schedule and cut sheets. 2. Receptacle outlets shall be computed at a minimum of 180 VA each yoke per NEC 220.3 (B) (9). For example, Ckt 2 shall be counted at 900VA, not 540. Typical. 3. Since the maximum fuse size has been specified for HP 1 & 2, a fuse must be used. 4. Specify conduit and conductor size and type. 5. Provide power requirements for the new WH on Sheet MP1. 6. Please verify with the manufacturer that the WH is cord-connected. 7. It is not clear whether 25% of lighting VA has been added as continuous load on panel schedule calculation. Please address as necessary. 8. Provide load calculations for electrical service. 9. Provide Available fault current at service and at New Panel A. Show fault calculations. 10. Address equipment grounding per NEC Part VI. |
| 11/18/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/21/2005 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 11/21/2005 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 11/21/2005 | DROBEY1 | ZONING | REVIEW | Needs Review | |
| 11/21/2005 | DROBEY1 | FIRE | REVIEW | Needs Review |