Permit Number: T05CM05788
Parcel: 14029007C

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05788
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2005 ANY ENGINEERING REVIEW Approved
11/18/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide riser diagram for water and show the pipe sizes.
11/18/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM05788 11/18/05

1. Provide a Lighting fixture schedule and cut sheets.
2. Receptacle outlets shall be computed at a minimum of 180 VA each yoke per NEC 220.3 (B) (9). For example, Ckt 2 shall be counted at 900VA, not 540. Typical.
3. Since the maximum fuse size has been specified for HP 1 & 2, a fuse must be used.
4. Specify conduit and conductor size and type.
5. Provide power requirements for the new WH on Sheet MP1.
6. Please verify with the manufacturer that the WH is cord-connected.
7. It is not clear whether 25% of lighting VA has been added as continuous load on panel schedule calculation. Please address as necessary.
8. Provide load calculations for electrical service.
9. Provide Available fault current at service and at New Panel A. Show fault calculations.
10. Address equipment grounding per NEC Part VI.
11/18/2005 ROBERT SHERRY WATER REVIEW Approved
11/18/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/21/2005 DROBEY1 ZONING REVIEW Needs Review
11/21/2005 DROBEY1 WWM REVIEW Needs Review
11/21/2005 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
11/21/2005 DROBEY1 FIRE REVIEW Needs Review