Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM05761
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/16/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/16/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide cleanout for the new 3" waste pipe 2. Resize the water piping per the submitted calculations. 3. Show the size of the waste pipe from the lavatories. |
11/16/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/16/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/16/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide a mechanical plan. 2.Revise the duct insulation per Section 803.2.8, IECC 2003. |
11/17/2005 | DROBEY1 | FIRE | REVIEW | Needs Review | |
11/17/2005 | DROBEY1 | WWM | REVIEW | Needs Review | |
11/17/2005 | DROBEY1 | ZONING | REVIEW | Needs Review | |
11/17/2005 | DROBEY1 | ENGINEERING | REVIEW | Needs Review |