Permit Number: T05CM05753
Parcel: 124060440

Address:
318 N PARK AV

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T05CM05753
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2005 GBONILL1 BUILDING-RESIDENTIAL REVIEW Needs Review
12/01/2005 SUZANNE BOHNET ENGINEERING REVIEW Denied DATE: December 1, 2005
ACTIVITY NUMBER: T05OT02841 / T05CM05753
PROJECT NAME: El Capitan Townhome Repairs
PROJECT ADDRESS: 318 N. Park Avenue
PROJECT REVIEWER: Suzanne Bohnet

FLOODPLAIN USE PERMIT IS DENIED

RESUBMITTAL REQUIRED: SITE PLAN

The following items must be corrected:

1. Add a note, indicating the structure lies within a mapped FEMA Special Flood Hazard Area Zone AE, referencing the FIRM panel number 04019C 2227K, effective date February 8, 1999.

2. Please include the Water Surface Elevation (WSE) on the Site Plan. From interpolation, the WSE for this structure is approximately 2400.6' above mean sea level (amsl) per the National Geodetic Vertical Datum (NGVD '29).

3. Add a note to the site plan indicating the vertical datum used for the finished floor elevation (FFE) and the WSE.

4. Please note the above requested information must be on the site plan. The site plan will not be approved unless the FFE and WSE for the structure have been provided.