Permit Number: T05CM05738
Parcel: 13018001J

Address:
4010 E 29TH ST

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM05738
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM05738 11/15/05

1. Mechanical calls for 208 V power. Electrical provides 240V.
2. ReCheck service calculations.
11/15/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/18/2005 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review