Permit Number: T05CM05714
Parcel: 11105076B

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T05CM05714
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM05714 1/9/06

1. Ckt N-10, revised to power Drinking Fountain, still powers lighting on Sheet E2.0.
2. New J-Box references NEC 37. There is no Article 37 in the National Electrical Code.
3. Conductor between the new J-Box and Panel N, #4, has ampacity of 85A. Not sufficient for the load on the panel or its overcurrent protective device.
4. Ground and bond is #20, below the minimum sizing. Did you intend 2/0?
5. Phase A totals to 21105 VA, not 18825. Draws 176A, which is greater than the rating of the circuit.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2007 GERARDO BONILLA OUT TO CUSTOMER Approved