| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/09/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM05714 1/9/06 1. Ckt N-10, revised to power Drinking Fountain, still powers lighting on Sheet E2.0. 2. New J-Box references NEC 37. There is no Article 37 in the National Electrical Code. 3. Conductor between the new J-Box and Panel N, #4, has ampacity of 85A. Not sufficient for the load on the panel or its overcurrent protective device. 4. Ground and bond is #20, below the minimum sizing. Did you intend 2/0? 5. Phase A totals to 21105 VA, not 18825. Draws 176A, which is greater than the rating of the circuit. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/12/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Approved |