Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/17/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
04/17/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the hood and the back supply plenum are to be mounted. Reference Sections 106.3.1 and 304.1, IMC 2000. 2. Revise the size of the grease duct to maintain a minimum velocity of 1500 fpm. Reference Section 506.3.5, IMC 2000. |
04/20/2006 | AKLAPPE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |