Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM05714
Parcel: 11105076B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM05714
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/17/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the hood and the back supply plenum are to be mounted. Reference Sections 106.3.1 and 304.1, IMC 2000.
2. Revise the size of the grease duct to maintain a minimum velocity of 1500 fpm. Reference Section 506.3.5, IMC 2000.
04/20/2006 AKLAPPE1 BUILDING-COMMERCIAL REVIEW Needs Review