Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM05714
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/29/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved. Show how the new water piping relates to the existing water supply system. Clarify keynotes 6 and 2 on sheet P1.0. Reference Section 101.5.1, UPC 1994. 2. The water pressure regulator previously referenced in keynote 32 (sheet P1.0) and shown adjacent to the reduced pressure backflow preventer on the plumbing plan has disappeared from the keynotes and plumbing plan. It is, however, still shown in the water calculations. Please clarify. Reference Appendix A, UPC 1994. 3. Comment not addressed. Include the water demand of the new evaporative cooler in the demand calculations. Reference Section 610.1, UPC 1994. 4. Comment not addressed. Provide an automatic shutoff valve for the gas service to the range. 5. Comment not addressed. Include the hose bibb (detail 3/M1.1) and evaporative cooler in the water demand calculations. Show the piping on the plans and riser diagrams. |
03/29/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Ventilation for restrooms in public spaces requires a minimum of 75 CFM of mechanical exhaust per water closet or urinal. Reference Table 403.3, IMC 2000. 2. The specified Greenheck Type I backshelf hood is not a compensating hood. Revise detail 1/M1.1 to correspond to the specified hood. Show how the hood and the back supply plenum are to be mounted. Reference Sections 106.3.1 and 304.1, IMC 2000. Note: revise keynote 8, sheet A1.0 to coordinate with the Type I hood requirement. 3. Revise the size of the grease duct to maintain a minimum velocity of 1500 fpm. Reference Section 506.3.5, IMC 2000. 4. Show that the installation of the hood complies with the clearance requirements of Section 507.10, IMC 2000 (detail 1/M1.1 shows no clearances between the double 2x8's and the hood). |
03/30/2006 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/07/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Comply to mechanical exam. comments in regards to exhaust hood. |