Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM05706
Parcel: 14029003H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05706
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2006 JMORALE1 WWM REVIEW Needs Review
11/14/2005 JOSE ORTIZ ENGINEERING REVIEW Approved
11/15/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
11/15/2005 JIM EGAN FIRE REVIEW Approved
11/16/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/16/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
11/16/2005 ROBERT SHERRY WATER REVIEW Approved
11/16/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM05706 11/16/05

1. Provide panel and circuit number for new receptacles.
2. Indicate location of panel on plans.
3. Demonstrate that panel and feeder are not overloaded with the receptacle addition.
11/16/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved