Permit Number: T05CM05703
Parcel: 13314459C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM05703
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 12/12/05
ACTIVITY NUMBER: T05CM05703
PROJECT NAME: ELEVATOR
PROJECT ADDRESS: 6300 EL. DORADO PLAZA
ARCHITECT / ENGINEER: PHIL SWAIM
PROJECT REVIEWER: CHRISTY FOREMAN


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.


1) Page 5 of 6 special note of shop drawings. Clarify / justify wind loading effects are not considered in these calculations. Consult manufacturer.
Spoke with elevator supplier. I need clarification. Structural engineer designed framework to withstand wind loads but there is no coordination of how independant frame of elevator is attached to structural framework. Shop drawings specify elevator structure is not designed to withstand wind loads. Please justify that elevator meets structural requirements of the 2003 IBC.
2) Elevator / lift is not being reviewed for ADA or ANSI A117.1 2003 requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/19/2006 GBONILL1 OUT TO CUSTOMER Completed
01/19/2006 SUE REEVES REJECT SHELF Completed