Permit Number: T05CM05703
Parcel: 13314459C

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T05CM05703
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM05703 12/7/05

1. Per NEC 620.22 (A), car light any receptacles in the elevator shall have their own branch circuit, the overcurrent device of which is located in the elevator control room/space. Also note 620.53 as applicable. Willing to discuss. It appears that Ckt 18 fulfills the requirements of 620.23, the following section.
2. Provide a separate branch circuit for the Hoistway Pit Lighting and Receptacles per NEC 620.24. Willing to discuss.
3. Disconnecting means for elevator supply conductors shall be either an enclosed externally operable fused motor circuit switch or circuit breaker capable of being locked in the open position. The Motor Rated Single Pole Switch specified does not appear to meet these criteria.
12/08/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Needs Review
12/08/2005 SUZANNE BOHNET ENGINEERING REVIEW Approved
12/08/2005 JIM EGAN FIRE REVIEW Approved
12/08/2005 MICHAEL ST. PAUL ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2005 CINDY AGUILAR OUT TO CUSTOMER Completed