Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T05CM05703
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/07/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM05703 12/7/05 1. Per NEC 620.22 (A), car light any receptacles in the elevator shall have their own branch circuit, the overcurrent device of which is located in the elevator control room/space. Also note 620.53 as applicable. Willing to discuss. It appears that Ckt 18 fulfills the requirements of 620.23, the following section. 2. Provide a separate branch circuit for the Hoistway Pit Lighting and Receptacles per NEC 620.24. Willing to discuss. 3. Disconnecting means for elevator supply conductors shall be either an enclosed externally operable fused motor circuit switch or circuit breaker capable of being locked in the open position. The Motor Rated Single Pole Switch specified does not appear to meet these criteria. |
12/08/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
12/08/2005 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
12/08/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
12/08/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
12/08/2005 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |