Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM05684
Parcel: 125091980

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T05CM05684
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied 1) The calculation denoted as delta 1 on sheet G1.0 labeled NEW SUPERIMPOSED LOADS, shows an
allowable load of 57 psf. for a 6 " thick plank/22' span and is referred to a table on sheet M2.0 The
table shows in the horiz. line the nominal moment
which is not shown on calc`s and also the series
which also is not shown on plans. So if 57 psf is to be used then specify the series (the correct one) or the
nominal moment(verify with calcs). Show these on plans.
02/08/2006 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Denied 1.Provide the existing service lateral conductors,insulation,conductor type,quantity etc. .2 Provide the total load on the existing service.3.See attached.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/22/2006 JMORALE1 OUT TO CUSTOMER Completed
02/22/2006 SUE REEVES REJECT SHELF Completed