Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T05CM05684
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/01/2006 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | 1) The calculation denoted as delta 1 on sheet G1.0 labeled NEW SUPERIMPOSED LOADS, shows an allowable load of 57 psf. for a 6 " thick plank/22' span and is referred to a table on sheet M2.0 The table shows in the horiz. line the nominal moment which is not shown on calc`s and also the series which also is not shown on plans. So if 57 psf is to be used then specify the series (the correct one) or the nominal moment(verify with calcs). Show these on plans. |
02/08/2006 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1.Provide the existing service lateral conductors,insulation,conductor type,quantity etc. .2 Provide the total load on the existing service.3.See attached. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/22/2006 | JMORALE1 | OUT TO CUSTOMER | Completed |
02/22/2006 | SUE REEVES | REJECT SHELF | Completed |