Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T05CM05684
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/06/2006 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE STRUCTURAL CALCULATIONS JUSTIFYING THE EXISTING ROOF IS ADEQUATE TO CARRY NEW LOAD (VERTICAL LOAD). |
| 01/06/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/06/2006 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/06/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM05684 01/06/06 Provide maintenance receptacle. Reference NEC 210.63. |