Permit Number: T05CM05683
Parcel: 114490160

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T05CM05683
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2006 SEPTIC APPROVAL WWM REVIEW Denied CALLED CUSTOMER, NEED TO KNOW IF ADDING SF OR BEDROOMS ON PLUMBING (EXSISTING 750 GAL S004)
02/16/2006 LINHART PETERSEN POERS ASSOC. 2ND PARTY REVIEW REVIEW Denied February 16, 2006 CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. T05CM05683
LP2A Job No. 2060161.012

City of Tucson
201 N. Stone Ave. 1st Floor
Tucson, AZ 85701

Re: Plan Review: Egan SFR Addition/Remodel
Address: 8029 E. Tanque Verde

Linhart Petersen Powers Associates (LP2A), a Bureau Veritas Company, has completed a review of the following documents on behalf of the City of Tucson:

1. Plans: One (1) set of plans (16 sheets A1.0 through E1.1) dated November 3, 2005 and stamped by Benjamin W. Cole and Janelle L. Perry.

2. Truss Calculations: None provided.

Structural Calculations: None provided.

Energy Compliance: None provided.


These documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes (i.e., State of Arizona and Tucson amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC).

Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded.


Sincerely,

LINHART PETERSEN POWERS ASSOCIATES
A Bureau Veritas Company




Randy McCoy, Senior Plans Examiner
ICC Plans Examiner









RM:pc c:/tucson\2060161.012pc1
enclosures



Re: Stories: One
Fire Sprinklers: No
Building Area (sq. ft.): 3954 (livable)
1903 (patio)


A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2003 International Residential Code.

B. Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance.

C. These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.).

ARCHITECTURAL COMMENTS:

Sheet A1.0 attached to plan set twice. R106.

Clarify note for area at proposed bar in new outdoor room. Sheet S1.0. R106.

Provide footings for 8X8 king posts in center of floor in new outdoor room, porch off of kitchen and master suite. Sheet S1.0. R106.

Please correct master suite section keynotes 9, 15 and 22. Sheet A6.0. IRC 106.

Provide descriptions of beams for porch of kitchen. Sheet S2.0. IRC 106.

Provide posts for porches on framing plan. Sheet S2.0. R106.

Please correct keynote 6 on framing plan. Sheet S2.0. R106.

Please correct all 2000 IRC reference to 2003 IRC. R106.

MECHANICAL, ELECTRICAL AND PLUMBING COMMENTS:

Provide combustion air for gas water heater. Sheet M1.0. R17.

Indicate the temperature and pressure relief line from the water heater to the exterior of the building. Sheet P2. P2803.6.1.

Panel schedule for panel W, specifies a 200 amp panel. The one line diagram specifies a 100 amp panel. Please clarify sheet. E1.0. R106.

Specify the service conductor from 400 amp panel to Panel A. Sheet E1.0. E3503

If you have any questions regarding the above comments, please contact Randy McCoy at (520) 820-1980 between 8:00 A.M. to 5:00 P.M., M-F.