Permit Number: T05CM05678
Parcel: 107120690

Review Status: Completed

Review Details: SITE

Permit Number - T05CM05678
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2005 JIM EGAN FIRE REVIEW Approved
11/18/2005 ANDREW CONNOR NPPO REVIEW Denied 1. Submit NPPO plan per DS 2-15.0. Include an aerial photograph, taken within a maximum of three (3) years of submittal, at a minimum scale of 1" = 60' showing the site's boundaries, the locations of all Protected Native Plants within those boundaries, and the plants' identification numbers keyed to the inventory list in Sec. 2-15.3.1.A.2. Any aerial photograph submitted, which was taken more than one (1) year prior to submittal, shall be accompanied by a letter stating that the site is substantially unchanged from the date of the aerial photograph.
11/18/2005 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Submit NPPO plan per DS 2-15.0. Include an aerial photograph, taken within a maximum of three (3) years of submittal, at a minimum scale of 1" = 60' showing the site's boundaries, the locations of all Protected Native Plants within those boundaries, and the plants' identification numbers keyed to the inventory list in Sec. 2-15.3.1.A.2. Any aerial photograph submitted, which was taken more than one (1) year prior to submittal, shall be accompanied by a letter stating that the site is substantially unchanged from the date of the aerial photograph.

2. Additional comments may apply
12/02/2005 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens FOR: David Rivera
Senior Planner Principal Planner

PROJECT:T05CM05678
2921 N. Geronimo
Apartments
Site Plan

Transmittal date:1st Review 12-05-05

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Per DS 2-02.2.1.6 Provide the last approved site plan clearly indicating the approved setbacks, uses, and number of existing bedrooms for existing structures. Indicate on the new site plan the perimeter yard setbacks and front street setbacks for the existing structures.

2. Per DS 2-02.2.1.7 The perimeter yard setbacks indicated for the new apartments must be from the end of the "wing" walls along the north and south property lines. Either remove "wing" walls or relocate the structures in order to comply with the required 10' perimeter yard setback.

3. Per DS 2-02.2.1.8 The handicap ramp indicated inside of the van accessible access aisle is not allowed. Relocate the ramp to the sidewalk in front of the access aisle.

4. Per DS 2-20.2.1.9 The bicycle parking spaces indicated in detail #2 are showing decomposed granite as a base. The site plan shows decomposed granite as a landscape cover to the south of the bicycle parking spaces but does not indicate granite in the parking space. Please clarify.

The bicycle parking spaces do not appear to be visible from the public right of way therefore directional signage will be required as per D 2-09.5.1.

5. Per DS 2-02.2.1.11 Provide a dimension of the PAAL located to the north of the existing four plex.

6. Per DS 2-02.2.1.12 The truncated domes indicated on the site plan are to be located at the edge of pavement adjacent to the access aisles or cross walks not at the bottom of the ramps as indicated.

If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000.
12/06/2005 TERRY STEVENS ZONING HC SITE REVIEW Denied see zoning comments
12/12/2005 JOSE ORTIZ ENGINEERING REVIEW Denied To: Client Robert Lanning
DATE: January 5, 2005
FROM: Jose E. Ortiz, PE
Engineering Division


SUBJECT: 2921 N. Geronimo Ave - Site plan T05CM05678 (First Review) - T13S, R13E, Section 36

RESUBMITTAL REQUIRED: Site Plan

The Site Plan (SP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. Please label lot dimensions and bearings per D.S. 2-02.2.1.5
3. If applicable, all easement of record must be graphically shown on the plan together with recording docket and page per D.S. 2-02.2.1.20.
4. The existing contours indicate that existing storm water flows east to west, but proposed flow arrows are set to flow west to east. How is this going to be done without dealing with differential grading? For clarification on how proposed drainage is to be handled please provide proposed spot elevations as pertinent per D.S. 2-02.2.1.16.
5. Please provide proposed spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
6. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
7. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
8. List the consulting engineer and the owner/developer on the plans with the pertinent information.
9. Add note: "Depress all landscaped areas 6" maximum for water harvesting".
10. Provide water harvesting around new units (7-12). This location is the true low point of the over all site.
11. Please provide openings in curb to relieve nuisance ponding in low points on paving.
12. Solid Waste vehicles backing into a striped pedestrian walkway is not an ideal situation. Is there an alternate location for either the refuse area or the walkway to prevent this conflict?




If you have any questions, I can be reached at 791-5550 x1191 Jose.Ortiz@tucsonaz.gov
Jose E. Ortiz
Civil Engineer

Final Status

Task End Date Reviewer's Name Type of Review Description
12/16/2005 DELMA ROBEY OUT TO CUSTOMER Completed