Permit Number - T05CM05672
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/13/2006 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | .. T05CM05672-1 .. 4500 N ORACLE ROAD #128 .. STRIDE RITE .. DGL .. 2nd REVIEW .. 1/17/06 .. S1. See prior comment S1. Provide and locate : 1. Vertical grab bar required by, ANSI Sec 604.5, 2. Toilet paper dispenser location per ANSI Sec 604.7, ref drawings A.01 and A.52. (Provide toilet conforming to IBC Section 11, 34 and ANSI A117.1-2003 ed.) If you wish : 1. You may revise this submittal at our counter and I would review it over-the-counter for items listed in comment S1. 2. You may revise the application to include the shelving detailed on drawing S1, which requires Special Inspection for the Expansion Anchors and delete the related note on A.00. Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/24/2006 | JMORALE1 | OUT TO CUSTOMER | Completed |
| 01/24/2006 | SUE REEVES | REJECT SHELF | Completed |