Permit Number: T05CM05672
Parcel: 10511061R

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05672
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/17/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
11/22/2005 JIM EGAN FIRE REVIEW Approved
11/22/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
11/23/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/23/2005 ROBERT SHERRY WATER REVIEW Approved
11/23/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/25/2005 GERRY KOZIOL WWM REVIEW Passed
11/30/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T05CM05672 .. 4500 N ORACLE ROAD #128 .. STRIDE RITE .. DGL .. 1ST REVIEW .. 12/1/05 ..

S1. Provide notes on rollup grill ref . drawing A.52 details 1 and 5, conforming to IBC Section 402.11, 1, 2, 3, and 4.
S2. Provide toilet conforming to IBC Section 11, 34 and ANSI A117.1-2003 ed.
S3. Show where 20% of Project Valuation is spent on accessibility per IBC Section 3409.6.
S4. Provide structural calculations and details on the drawings, sealed and signed by Registrant, for storefront and roll down grill, including connections to existing structure.
S5. Separate building permit required for shelving over 8 feet high.
S6. Clarify occupant load calculation on drawing A.00, per IBC Section 1004, Table 1004.1.2 , reductions are not allowed.
S7 Separate permits required for signs.


Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.
12/20/2005 DAN CASTRO ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/04/2006 BETH GRANT OUT TO CUSTOMER Completed
01/04/2006 SUE REEVES REJECT SHELF Completed