Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T05CM05667
Parcel: 11005014C

Address:
2940 N SWAN RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05667
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2005 JIM EGAN FIRE REVIEW Approved
11/10/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/10/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) NEED TO PROVIDE A WATER FOUNTAIN FOR WHEEL CHAIR AND STANDING SEE ANSI A117.1 2003 SECTION 602.
2) CLARIFY KNEE CLEARANCE PER SECTION 306.3.
3) RAMP REQUIREMENTS FOR 1:10 MAX. ALLOWABLE RISE = 6"
4) SEE SECTION 505.10.1 FOR HANDRAIL REQUIREMENTS.
5) CLEAR WIDTH REQUIREMENTS SEE 405.5
6) CLARIFY DOOR CLEARANCE FOR WOMEN'S RESTROOM.
7) CLARIFY HAVE 42" CLEAR FOR ACCESSIBLE W.C. SEE FIG. 604.8.3.
8) CLARIFY MANUVERABILTY AT BOTTOM OF RAMP. SEE FIG 304.3
11/10/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Coordinate mechanical general note 7 with the mechanical plan. If the plan is correct, show that the exhaust ducts do not discharge over a walkway. Reference Section 401.5.2, IMC 2000.
2. The outdoor air calculation calls for 225 CFM of outside air per restroom but only 100 CFM of outside air is scheduled for each fan coil unit. Show how this complies with Section 403.2.2, IMC 2000.
3. Clarify the source of the additional outside air.
11/10/2005 HEATHER THRALL ZONING REVIEW Approved
11/10/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
11/10/2005 ANY ENGINEERING REVIEW Approved
11/21/2005 GBONILL1 WWM REVIEW Needs Review
11/21/2005 GBONILL1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/21/2005 GBONILL1 OUT TO CUSTOMER Completed