Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM05667
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/10/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 11/10/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 11/10/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) NEED TO PROVIDE A WATER FOUNTAIN FOR WHEEL CHAIR AND STANDING SEE ANSI A117.1 2003 SECTION 602. 2) CLARIFY KNEE CLEARANCE PER SECTION 306.3. 3) RAMP REQUIREMENTS FOR 1:10 MAX. ALLOWABLE RISE = 6" 4) SEE SECTION 505.10.1 FOR HANDRAIL REQUIREMENTS. 5) CLEAR WIDTH REQUIREMENTS SEE 405.5 6) CLARIFY DOOR CLEARANCE FOR WOMEN'S RESTROOM. 7) CLARIFY HAVE 42" CLEAR FOR ACCESSIBLE W.C. SEE FIG. 604.8.3. 8) CLARIFY MANUVERABILTY AT BOTTOM OF RAMP. SEE FIG 304.3 |
| 11/10/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Coordinate mechanical general note 7 with the mechanical plan. If the plan is correct, show that the exhaust ducts do not discharge over a walkway. Reference Section 401.5.2, IMC 2000. 2. The outdoor air calculation calls for 225 CFM of outside air per restroom but only 100 CFM of outside air is scheduled for each fan coil unit. Show how this complies with Section 403.2.2, IMC 2000. 3. Clarify the source of the additional outside air. |
| 11/10/2005 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 11/10/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/10/2005 | ANY | ENGINEERING | REVIEW | Approved | |
| 11/21/2005 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 11/21/2005 | GBONILL1 | WATER | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/21/2005 | GBONILL1 | OUT TO CUSTOMER | Completed |