Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2005 GERRY KOZIOL WWM REVIEW Approved
11/07/2005 ANDREW CONNOR NPPO REVIEW Passed
11/28/2005 SREEVES1 ZONING REVIEW Passed approved last workflow
11/28/2005 LOREN MAKUS ENGINEERING REVIEW Approved
12/06/2005 WILDAN 2ND PARTY REVIEW REVIEW Denied December 5, 2005

City of Tucson
Development Services Department
201 North Stone Avenue
Tucson, AZ 85701

RE: BARCENAS RESIDENCE – 1ST REVIEW
CITY OF TUCSON LOG NO T05CM05607
WILLDAN PROJECT NO. 13881-5028

The initial review for the above project has been completed. The following items reflect original comments, which remain unaddressed and require a written response indicating any action to be taken. In order to facilitate a shorter back-check time, all corrections and revisions shall be made on the original plans and two new COMPLETE sets of prints shall be returned along with all redline prints. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets as well as highlighting all changes with appropriate revision number, revision date, and “cloud bubbles”. Pen or pencil corrections on final prints will not be acceptable. Please return comment drawings with your re-submittal. Should you have questions regarding the comments herein, please contact your plans examiner John Stigalt.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
R-3
Patio N/A IIIB 1717
240 No Yes

GENERAL COMMENTS:
This project has been reviewed for conformance with the 2003 IRC, 1997 UAC, 2000 IMC, 2000 IECC, 2002 NEC codes with local modifications, and the 1994 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan.

ARCHITECTURAL COMMENTS:

Sheet 2
There is a misprint on the code section number referenced. The correct code section number is R308.4 item #5. Reference section R106.1.1 IRC.

STRUCTURAL COMMENTS:
Items submitted reviewed and accepted

PLUMBING COMMENTS:

Sheet 2
Annotate on the plans that the T & P relief valve discharge pipe will terminate no more than 24” and no less than 6” above the floor or grade. Reference section 608.5 UPC.

In note #16 please remove the reference to the 2003 IRC and replace with the reference from the 94 UPC. If the 2003 IRC wishes to be utilized, an appeal to the Building Official will need to be applied for. Unless the appeal is granted, all references must be to the 94 UPC. If granted all references are to be to the 2003 IRC plumbing section. The correct UPC code section number is 410.4 UPC. Reference the City of Tucson adopted codes.




Show on the plans that the vent for the water closet will be the same size and undiminished for the entire length. Reference section 905.4 UPC.


MECHANICAL COMMENTS:

Sheet 7
Annotate on the plans the developed lengths to each of the gas burning appliances and list the CFH to each appliance. Reference the City of Tucson submittal requirements.


ELECTRICAL COMMENTS:

Sheet 6
Please provide cut sheets for the exterior light fixtures and coordinate them with the calculations noted on the plans. The calculations shall be based on the maximum wattage that the fixture is listed for which will provide the maximum lumens per fixture. Reference the City of Tucson Outdoor Lighting Code.


ENERGY CODE COMMENTS:
Reviewed and accepted


ACCESSIBILITY COMMENTS:
Not part of this review



Should you have questions regarding the comments herein, please contact your plans examiner John Stigalt.







Sincerely

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/sb