11/18/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved 1. The proposed sequence of operation for the restroom exhaust fans does not prevent recirculation of the air from the restrooms.
2. Revise the ventilation calculations to comply with Section 403.3.2, IMC 2000.