Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM05603
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/18/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | 1. The proposed sequence of operation for the restroom exhaust fans does not prevent recirculation of the air from the restrooms. 2. Revise the ventilation calculations to comply with Section 403.3.2, IMC 2000. |
11/18/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
11/18/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |