| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/18/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | 1. The proposed sequence of operation for the restroom exhaust fans does not prevent recirculation of the air from the restrooms. 2. Revise the ventilation calculations to comply with Section 403.3.2, IMC 2000. |
| 11/18/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 11/18/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |