Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM05603
Parcel: 12708187F

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM05603
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/18/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved 1. The proposed sequence of operation for the restroom exhaust fans does not prevent recirculation of the air from the restrooms.
2. Revise the ventilation calculations to comply with Section 403.3.2, IMC 2000.
11/18/2005 GERRY KOZIOL WWM REVIEW Approved
11/18/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved