Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM05603
Parcel: 12708187F

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05603
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2005 JIM EGAN FIRE REVIEW Approved
11/14/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The trap and trap arm for a lavatory (1-1/4" tailpiece) cannot be 2". Reference Section 1003.3, UPC 1994.
2. The maximum length for a 1-1/2" trap arm is 3'-6". Reference Section 1002.2, UPC 1994.
3. Show how the allowable friction loss of 5 psi per 100 feet was determined.
4. The minimum font size is 10 points.
11/14/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
11/14/2005 ROBERT SHERRY WATER REVIEW Approved
11/14/2005 TERRY STEVENS ZONING REVIEW Approved
11/14/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how recirculation of the supply air from the restrooms will be prevented. Reference Section 403.2.1 (3), IMC 2000.
2. Revise the outside air calculations to include the conference room. Reference Sections 403.3 and 403.3.2, IMC 2000.
3. Revise the ductwork insulation to comply with the requirements of Section 803.2.8, IECC 2003.
4. Show that the minimum exhaust from the restrooms complies with the requirements of Section 403.3, IMC 2000.
11/14/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
11/14/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
11/18/2005 CAGUILA1 WWM REVIEW Needs Review