Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM05603
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/14/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 11/14/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The trap and trap arm for a lavatory (1-1/4" tailpiece) cannot be 2". Reference Section 1003.3, UPC 1994. 2. The maximum length for a 1-1/2" trap arm is 3'-6". Reference Section 1002.2, UPC 1994. 3. Show how the allowable friction loss of 5 psi per 100 feet was determined. 4. The minimum font size is 10 points. |
| 11/14/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/14/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/14/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 11/14/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how recirculation of the supply air from the restrooms will be prevented. Reference Section 403.2.1 (3), IMC 2000. 2. Revise the outside air calculations to include the conference room. Reference Sections 403.3 and 403.3.2, IMC 2000. 3. Revise the ductwork insulation to comply with the requirements of Section 803.2.8, IECC 2003. 4. Show that the minimum exhaust from the restrooms complies with the requirements of Section 403.3, IMC 2000. |
| 11/14/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/14/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 11/18/2005 | CAGUILA1 | WWM | REVIEW | Needs Review |