Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM05506
Parcel: 13110034A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM05506
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/16/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 12/16/05
ACTIVITY NUMBER: T05CM05506
PROJECT NAME: BUCKEYE CHECK CASHING
PROJECT ADDRESS:5504 E. 22ND ST., STE 100
ARCHITECT / ENGINEER: ERIC LEIBSOHN & ASSOC.
PROJECT REVIEWER: CHRISTY FOREMAN


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Special Inspection form will be required for masonry / steel reinforcement and structural welding before permit can be issued. Inspectors submitted are not on our approved list.
2) Clarify roof framing plan location of HVAC units.Provide structural calculations justifying existing roof framing can support the new load for the HVAC equipment.
12/28/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/28/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show the size, routing, and termination of the condensate drains. Reference Section 307.2, IMC 2000 and Section 807.2, UPC 1994.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/03/2006 GBONILL1 OUT TO CUSTOMER Completed
01/03/2006 SUE REEVES REJECT SHELF Completed