Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM05506
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/16/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 12/16/05 ACTIVITY NUMBER: T05CM05506 PROJECT NAME: BUCKEYE CHECK CASHING PROJECT ADDRESS:5504 E. 22ND ST., STE 100 ARCHITECT / ENGINEER: ERIC LEIBSOHN & ASSOC. PROJECT REVIEWER: CHRISTY FOREMAN TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1) Special Inspection form will be required for masonry / steel reinforcement and structural welding before permit can be issued. Inspectors submitted are not on our approved list. 2) Clarify roof framing plan location of HVAC units.Provide structural calculations justifying existing roof framing can support the new load for the HVAC equipment. |
| 12/28/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/28/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show the size, routing, and termination of the condensate drains. Reference Section 307.2, IMC 2000 and Section 807.2, UPC 1994. |