Permit Number: T05CM05506
Parcel: 13110034A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05506
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2005 JIM EGAN FIRE REVIEW Approved
10/31/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Coordinate the installation of the three ceiling-mounted exhaust fans with the electrical design. Reference Section 106.3.1, IMC 2000.
10/31/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a cleanout for the 3" building drain. Reference Section 707.11, UPC 1994.
2. Clarify if the proposed 2-way cleanout shown on 1/P-1 is an approved 2-way cleanout fitting or if it is to be a field-fabricated assembly composed of combination wye fittings. Fabricating 2-way cleanouts with combination wye fittings is in violation of Section 707.6, UPC 1994.
3. According to Tucson Water, the water pressure for this address has a range of 80 - 87 PSI. Provide a pressure regulator to limit the pressure to no more than 80 PSI. Reference Section 608.2, UPC 1994.
4. Clarify the size of reduced pressure backflow preventor proposed for this project; plan 1/P-2 shows a 1-1/2" unit but a 2" unit is specified.
5. Provide a detail to show how the water heater platform is to be anchored to the wall (detail 201/P-1). Reference Section 102.3.2, UPC 1994.
10/31/2005 ROBERT SHERRY WATER REVIEW Approved
11/02/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
11/03/2005 GERRY KOZIOL WWM REVIEW Approved
11/28/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 11/28/05
ACTIVITY NUMBER: T05CM05506
PROJECT NAME: BUCKEYE CHECK CASHING
PROJECT ADDRESS:5504 E. 22ND ST., STE 100
ARCHITECT / ENGINEER: ERIC LEIBSOHN & ASSOC.
PROJECT REVIEWER: CHRISTY FOREMAN


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Clarify existing fire wall hr. rating.
2) Clarify / justify wind load on sht. D-1 of structural calculations.
3) Clarify / justify live load reduction on span lintel @ 20'-0" opening sht. #1 structural calculations.
4) Sht. 1 structural calculations lateral wind justified per UBC 97 - Tucson has adopted the 2003 IBC.
5) Special Inspection form will be required for masonry / steel reinforcement and structural welding before permit can be issued.
6) Clarify roof framing plan location of HVAC units.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/07/2005 JMORALE1 OUT TO CUSTOMER Completed
12/07/2005 SUE REEVES REJECT SHELF Completed