Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM05506
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/31/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/31/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Coordinate the installation of the three ceiling-mounted exhaust fans with the electrical design. Reference Section 106.3.1, IMC 2000. |
| 10/31/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a cleanout for the 3" building drain. Reference Section 707.11, UPC 1994. 2. Clarify if the proposed 2-way cleanout shown on 1/P-1 is an approved 2-way cleanout fitting or if it is to be a field-fabricated assembly composed of combination wye fittings. Fabricating 2-way cleanouts with combination wye fittings is in violation of Section 707.6, UPC 1994. 3. According to Tucson Water, the water pressure for this address has a range of 80 - 87 PSI. Provide a pressure regulator to limit the pressure to no more than 80 PSI. Reference Section 608.2, UPC 1994. 4. Clarify the size of reduced pressure backflow preventor proposed for this project; plan 1/P-2 shows a 1-1/2" unit but a 2" unit is specified. 5. Provide a detail to show how the water heater platform is to be anchored to the wall (detail 201/P-1). Reference Section 102.3.2, UPC 1994. |
| 10/31/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/02/2005 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/03/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 11/28/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 11/28/05 ACTIVITY NUMBER: T05CM05506 PROJECT NAME: BUCKEYE CHECK CASHING PROJECT ADDRESS:5504 E. 22ND ST., STE 100 ARCHITECT / ENGINEER: ERIC LEIBSOHN & ASSOC. PROJECT REVIEWER: CHRISTY FOREMAN TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1) Clarify existing fire wall hr. rating. 2) Clarify / justify wind load on sht. D-1 of structural calculations. 3) Clarify / justify live load reduction on span lintel @ 20'-0" opening sht. #1 structural calculations. 4) Sht. 1 structural calculations lateral wind justified per UBC 97 - Tucson has adopted the 2003 IBC. 5) Special Inspection form will be required for masonry / steel reinforcement and structural welding before permit can be issued. 6) Clarify roof framing plan location of HVAC units. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/07/2005 | JMORALE1 | OUT TO CUSTOMER | Completed |
| 12/07/2005 | SUE REEVES | REJECT SHELF | Completed |