| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2006 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
| 04/19/2006 | CAGUILA1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 04/19/2006 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 10/28/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05EL02080 10/27/05 1. Provide TEP Available Fault Current at the service, or put the following note on the plans: "Contractor shall provide documentation from TEP of available fault current. All equipment shall be installed within its fault current rating. 2. Service shall be underground, unless there is an existing overhead service. 3. Plans shall comply with the Lighting Ordinance, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. Reference Section 3.4 Resumption of Use. |