Permit Number: T05CM05445
Parcel: 140122210

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05445
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/26/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/26/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/26/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
10/26/2005 ROBERT SHERRY WATER REVIEW Approved
10/26/2005 HEATHER THRALL ZONING REVIEW Approved
10/26/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/26/2005 RAUL PALMA PLUMBING-COMMERCIAL REVIEW Passed
10/27/2005 JIM EGAN FIRE REVIEW Approved
10/28/2005 GERRY KOZIOL WWM REVIEW Passed
10/28/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM05445 10/27/05

1. Ampacity of #1 Al is 100A per NEC Table 310.16. Not Sufficient for 103 A calculated load.
2. Fuse at 200A not sufficient to protect 100A feeder.
3. Fuse at 200A requires a #4 GND, not #6. Reference NEC Table 250.122.
4. If the receptacles on B-22 are intended to serve show windows, the VA shall be counted as 200 VA/LF. Reference NEC 220.12 (A). Please correct as necessary.