Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM05445
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/26/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 10/26/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/26/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/26/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/26/2005 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 10/26/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/26/2005 | RAUL PALMA | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 10/27/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/28/2005 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 10/28/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM05445 10/27/05 1. Ampacity of #1 Al is 100A per NEC Table 310.16. Not Sufficient for 103 A calculated load. 2. Fuse at 200A not sufficient to protect 100A feeder. 3. Fuse at 200A requires a #4 GND, not #6. Reference NEC Table 250.122. 4. If the receptacles on B-22 are intended to serve show windows, the VA shall be counted as 200 VA/LF. Reference NEC 220.12 (A). Please correct as necessary. |