Permit Number: T05CM05389
Parcel: 10511061R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM05389
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
11/07/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/07/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/08/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM05389 11/7/05

1. Show 1.25% for continuous load on panel schedule. This comment was made on the original submittal. Plans Examiner calculates a total of 88 amps if such load is added. Load Calculations on the side do not mean anything, as they apply the demand factor for loads which are not continuous, and Total Load Amps of 38 is not accurate for this panel.

PLEASE CONTACT PLANS EXAMINER AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS.