Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM05389
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/07/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/07/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 11/07/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 11/08/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM05389 11/7/05 1. Show 1.25% for continuous load on panel schedule. This comment was made on the original submittal. Plans Examiner calculates a total of 88 amps if such load is added. Load Calculations on the side do not mean anything, as they apply the demand factor for loads which are not continuous, and Total Load Amps of 38 is not accurate for this panel. PLEASE CONTACT PLANS EXAMINER AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. |