Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM05376
Parcel: 10818716A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05376
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2005 JOSE ORTIZ ENGINEERING REVIEW Approved
10/21/2005 HEATHER THRALL ZONING REVIEW Approved
10/24/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
10/24/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
10/24/2005 GERRY KOZIOL WWM REVIEW Approved
10/24/2005 JIM EGAN FIRE REVIEW Approved
10/24/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/24/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
10/24/2005 ROBERT SHERRY WATER REVIEW Approved