Permit Number: T05CM05369
Parcel: 10612017R

Review Status: Active

Review Details: COMMERCIAL TI

Permit Number - T05CM05369
Review Name: COMMERCIAL TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2009 GERRY KOZIOL WWM REVIEW Approved
10/21/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/21/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
10/27/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/27/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
10/27/2005 ROBERT SHERRY WATER REVIEW Approved
10/27/2005 JIM EGAN FIRE REVIEW Approved
10/27/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/27/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM05369 10/27/05

1. Provide TEP Available Fault Current at the service.
2. Electric Plan and Schedule indicate that the Panel to Suite 151 is existing. Line Diagram indictes this Panel is New. Please clarify.
3. Provide fault calculations to show AFC at new panel.
4. Provide fault current rating of new panel.
5. Show TEP service on scaled drawing.