Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL TI
Permit Number - T05CM05369
Review Name: COMMERCIAL TI
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 10/21/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 10/21/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 10/27/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/27/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/27/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/27/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/27/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/27/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM05369 10/27/05 1. Provide TEP Available Fault Current at the service. 2. Electric Plan and Schedule indicate that the Panel to Suite 151 is existing. Line Diagram indictes this Panel is New. Please clarify. 3. Provide fault calculations to show AFC at new panel. 4. Provide fault current rating of new panel. 5. Show TEP service on scaled drawing. |