Permit Number: T05CM05332
Parcel: 10821328B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05332
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2005 JIM EGAN FIRE REVIEW Approved
10/19/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Coordinate the proposed fixtures with the architectural drawings (e.g. dishwasher, conection for refrigerator ice maker).
10/19/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY LOCATION, DISTANCE TRAVELED, AND ACCESSIBILTY OF RESTROOM FACILITIES.
2) PROVIDE FULL WALL SECTION FOR EACH CONDITION AND CLARIFY LATERAL BRACING IF REQUIRED. PROVIDE FLOOR BRACING FOR WALLS THAT ARE NOT FULL HEIGHT.
3) CLARIFY BREAKROOM CABINET HGT MEETS ACCESSIBILTY REQUIREMENTS ANSI A117.1 2003.
10/19/2005 ROBERT SHERRY WATER REVIEW Approved
10/19/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM05332 10/19/05

1. It appears that the load calculations consider other than general purpose receptacles counted at 180VA/EA, for the purpose of the demand factor allowed by NEC 220.13.
2. Please recheck Branch Circuits B-4, B-6, B-9, and B-28. My figures came to 1440, 1056, 1080, and 720 VA, respectively.
3. Ground the telephone system per NEC 800.40.
4. Add load on panel schedule for Ckt B-18.
5. Recheck service load calculations as appropriate.
10/19/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the return air is to reach the fan coil units.
11/08/2005 JMORALE1 ZONING REVIEW Needs Review
11/08/2005 JMORALE1 WWM REVIEW Needs Review
11/08/2005 JMORALE1 ENGINEERING REVIEW Needs Review