Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM05332
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/19/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
10/19/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Coordinate the proposed fixtures with the architectural drawings (e.g. dishwasher, conection for refrigerator ice maker). |
10/19/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) CLARIFY LOCATION, DISTANCE TRAVELED, AND ACCESSIBILTY OF RESTROOM FACILITIES. 2) PROVIDE FULL WALL SECTION FOR EACH CONDITION AND CLARIFY LATERAL BRACING IF REQUIRED. PROVIDE FLOOR BRACING FOR WALLS THAT ARE NOT FULL HEIGHT. 3) CLARIFY BREAKROOM CABINET HGT MEETS ACCESSIBILTY REQUIREMENTS ANSI A117.1 2003. |
10/19/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/19/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM05332 10/19/05 1. It appears that the load calculations consider other than general purpose receptacles counted at 180VA/EA, for the purpose of the demand factor allowed by NEC 220.13. 2. Please recheck Branch Circuits B-4, B-6, B-9, and B-28. My figures came to 1440, 1056, 1080, and 720 VA, respectively. 3. Ground the telephone system per NEC 800.40. 4. Add load on panel schedule for Ckt B-18. 5. Recheck service load calculations as appropriate. |
10/19/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show how the return air is to reach the fan coil units. |
11/08/2005 | JMORALE1 | ZONING | REVIEW | Needs Review | |
11/08/2005 | JMORALE1 | WWM | REVIEW | Needs Review | |
11/08/2005 | JMORALE1 | ENGINEERING | REVIEW | Needs Review |