Permit Number: T05CM05332
Parcel: 10821328B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM05332
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved 1) CLARIFY LOCATION, DISTANCE TRAVELED, AND ACCESSIBILTY OF RESTROOM FACILITIES. RESTROOMS APPEAR TO NOT BE ACCESSIBLE. CHAPT 3409.6 CLARIFY 20 % COST OF CONSTRUCTION IS BEING SPENT TOWARDS METTING ANSI A117.1 2003. CLARIFY MODIFACATIONS BEING MADETO ITEMS THAT ARE NOT NEW TO T.I. SPACE.

2) PROVIDE FULL WALL SECTION FOR EACH CONDITION AND CLARIFY LATERAL BRACING IF REQUIRED. PROVIDE FLOOR BRACING FOR WALLS THAT ARE NOT FULL HEIGHT. PROVIDE STRUCTURAL CALCS. TO JUSTIFY YOUR DETAIL. SEE SECTION 1621.1.2. SEE
DETAIL 5/A3 - HTT22 SIMPSON ANCHOR NEEDS TO BE INSTALLED AS SPECIED BY MANUFACTURER. WOOD 2X4 STUD NEED TO HAVE ATTACHMENT TO STRUCTURAL FRAMING. STRUCTURAL CALCULATIONS NEED TO JUSTIFY WHAT YOUR DETAIL SHOWS.
11/22/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
11/23/2005 HEATHER THRALL ZONING REVIEW Approved
11/23/2005 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/25/2005 BETH GRANT OUT TO CUSTOMER Completed