Permit Number: T05CM05331
Parcel: 10821328B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05331
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2005 JIM EGAN FIRE REVIEW Approved
10/19/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the piping material to comply with the requirements of Section 602.2.1, IMC 2000.
10/19/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
10/19/2005 ROBERT SHERRY WATER REVIEW Approved
10/19/2005 TERRY STEVENS ZONING REVIEW Approved
10/19/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Specify the duct insulation to be used on this project. Reference Section 803.2.8, IECC 2003
10/19/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM05331 10/19/05

1. Provide a circuit for the Water Heate indicated on Sheet P-1.
2. Circuits A-2 and A-4 have been used twice.
3. Ground telephone system per NEC 800.40. Not complete on Power Plan.
4. Circuit B-7, dedicated for the copier, has 4 receptacles.
5. Panel B has existing load which is not accounted for in the load calculations.
10/19/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/25/2005 DROBEY1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2005 DELMA ROBEY OUT TO CUSTOMER Completed