Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM05331
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/19/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/19/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the piping material to comply with the requirements of Section 602.2.1, IMC 2000. |
| 10/19/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/19/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/19/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 10/19/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Specify the duct insulation to be used on this project. Reference Section 803.2.8, IECC 2003 |
| 10/19/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM05331 10/19/05 1. Provide a circuit for the Water Heate indicated on Sheet P-1. 2. Circuits A-2 and A-4 have been used twice. 3. Ground telephone system per NEC 800.40. Not complete on Power Plan. 4. Circuit B-7, dedicated for the copier, has 4 receptacles. 5. Panel B has existing load which is not accounted for in the load calculations. |
| 10/19/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 10/25/2005 | DROBEY1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/25/2005 | DELMA ROBEY | OUT TO CUSTOMER | Completed |