Permit Number: T05CM05326
Parcel: 125076370

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05326
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/18/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
10/18/2005 HEATHER THRALL ZONING REVIEW Approved
10/19/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/19/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
10/19/2005 ROBERT SHERRY WATER REVIEW Approved
10/19/2005 JIM EGAN FIRE REVIEW Approved
10/19/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the restroom exhaust to comply with Section 401.5.2, IMC 2000.
10/19/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM05326 10/19/05

1. The 25A Water Heater is on a 20A circuit.
2. For the purpose of the feeder calculation, the track lighting shall be added at 75VA/LF. Since this is a clothing store, it is reasonable to consider that at 1.25% for continuous loading.
3. Water Heater is also not added to the Load Summary at bottom.
10/26/2005 KMEDINA1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/26/2005 KMEDINA1 OUT TO CUSTOMER Completed