Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM05326
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/18/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
10/18/2005 | HEATHER THRALL | ZONING | REVIEW | Approved | |
10/19/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
10/19/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/19/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
10/19/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
10/19/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the restroom exhaust to comply with Section 401.5.2, IMC 2000. |
10/19/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM05326 10/19/05 1. The 25A Water Heater is on a 20A circuit. 2. For the purpose of the feeder calculation, the track lighting shall be added at 75VA/LF. Since this is a clothing store, it is reasonable to consider that at 1.25% for continuous loading. 3. Water Heater is also not added to the Load Summary at bottom. |
10/26/2005 | KMEDINA1 | WWM | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/26/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |