Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM05181
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/13/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 10/13/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show the size, route, and termination point for the T&P relief for the water heater. |
| 10/13/2005 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/13/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/13/2005 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 10/13/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the ventilation for the project complies with Section 403.3, IMC 2000. 2. Show how recirculation of the air supplied to the restrooms will be avoided, 3. Provide an exhaust fan for room 115. |
| 10/13/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/13/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 10/19/2005 | GERRY KOZIOL | WWM | REVIEW | Approved |