Permit Number: T05CM05181
Parcel: 12208043A

Address:
4002 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05181
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2005 JIM EGAN FIRE REVIEW Approved
10/13/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show the size, route, and termination point for the T&P relief for the water heater.
10/13/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approved
10/13/2005 ROBERT SHERRY WATER REVIEW Approved
10/13/2005 HEATHER THRALL ZONING REVIEW Approved
10/13/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the ventilation for the project complies with Section 403.3, IMC 2000.
2. Show how recirculation of the air supplied to the restrooms will be avoided,
3. Provide an exhaust fan for room 115.
10/13/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
10/13/2005 LOREN MAKUS ENGINEERING REVIEW Approved
10/19/2005 GERRY KOZIOL WWM REVIEW Approved