Permit Number: T05CM05135
Parcel: 13409019L

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM05135
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2005 JIM EGAN FIRE REVIEW Approved
10/11/2005 JOSE ORTIZ ENGINEERING REVIEW Approved
10/13/2005 HEATHER THRALL ZONING REVIEW Approved
10/14/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/14/2005 ROBERT SHERRY WATER REVIEW Approved
10/14/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/18/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
10/18/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM05135 10/14/05

1. Provide GFI protected foot spa circuit per manufacturer's requirements.
2. Please revisit Phase C calculations per the tab on the drawings.
3. Specify conduit and conductor size and type.

10/18/05 See Comments 1 & 3 above.
11/18/2005 GERRY KOZIOL WWM REVIEW Approved