Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SITE ALL
Permit Number - T05CM05127
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/26/2006 | ANDREW CONNOR | LANDSCAPE | REVIEW | Denied | 1. Street landscape border is required along Mountain Ave. per LUC 3.7.2.4. Dimension landscape borders accordingly. 2. Fifty (50) percent or more of the street landscape border area must have shrubs and vegetative ground cover per LUC 3.7.2.4. Verify coverage and revise calculations as necessary on landscape plan. 3. All disturbed areas including adjacent right of ways shall be treated with ground cover such as decomposed granite to help reduce dust pollution per LUC 3.7.2.7. Revise note pertaining to decomposed granite as necessary. 4. A 6' wall for loading zone area must be provided to screen all residential zoned properties per LUC Table 3.7.2-I. Verify wall height to screen loading zone from property to the north. 5. Note: Within a vehicular use area, one (1) canopy tree is required for each 10 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.a. Revise note pertaining to canopy tree requirement on Sheet L3.2. 6. Refuse containers are to be placed so that the collection vehicle does not have to back into moving traffic, on or off the premises per DS 6-01.4.1.I. Refuse storage on Mountain must be re-located. |
| 02/08/2006 | TERRY STEVENS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Terry Stevens FOR: David Rivera Senior Planner Principal Planner PROJECT:T05CM05127 1435 E. 36th St. Park Villas Casitas Site Plan Transmittal date:2nd Review 2-09-06 COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. Zoning acknowledges your response to the following comment. The required documentation as indicated in your response was not provided with the resubmitted package. Please provide. The proposed site plan indicating a 5 acre parcel appears to have been recently split from a larger parcel. Provide documentation indicating the Zoning division of Development Services has approved the lot split. 2. A DSMR has been approved for this project. Please provide the DSMR case number and any conditions of the DSMR on the site plan. 3. In the parking calculations on page C1.1 change the note to reflect the actual number of parking spaces provided and not as an alternate bid amount. If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000. |
| 02/09/2006 | TERRY STEVENS | ZONING HC SITE | REVIEW | Approved | |
| 03/02/2006 | ELIZABETH EBERBACH | ENGINEERING | REVIEW | Denied | Per meetings this week, Architect to revise site plan for alternate location of solid waste pick-up. Resubmit revised SP for review. |