Permit Number: T05CM05124
Parcel: 140420150

Address:
2660 E MEDINA RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM05124
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2007 WILDAN 2ND PARTY REVIEW REVIEW Denied March 16, 2007



City of Tucson Development Services
P.O. Box 27210
Tucson, AZ 85726

RE: Residence Inn Marriott Deferred Truss Submittal – 2nd REVIEW
CITY OF TUCSON LOG NO. T05CM05124-R
WILLDAN PROJECT NO. 13881-7032

The second review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IBC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC, and the 2003 UPC. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Antonio Moya.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
N/A N/A N/A N/A N/A N/A

Special Inspection is required for the following items:
N/A

The following items are acceptable for deferred submittals:
N/A

STRUCTURAL COMMENTS:
Truss Calculations
The truss calculations are to be reviewed and accepted by the engineer of record prior to submittal to the City of Tucson. Reference IBC Section 106.3.4.2. COMMENT REMAINS: Please address the comments from the architect/engineer of record as noted on the truss design drawings (i.e. deflection criteria exceeded).

Provide the truss layouts for each floor and roof corresponding to the truss calculations. Reference IBC Section 106.1.1. COMMENT REMAINS: Please revise those layouts that are illegible per section 106.1.1 of the 2003 IBC.

Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb

Final Status

Task End Date Reviewer's Name Type of Review Description
03/27/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
03/27/2007 SUE REEVES REJECT SHELF Completed